BP112166 - #10 1850 Northfield

Interested in this application? Login to manage subscriptions to subscribe to updates!

Search Again
BP112166 - #10 1850 Northfield
Neighbourhood: Northfield    
Street Address: #10 1850 Northfield
Type of Application: Leasehold Improvements
File Number: BP112166
Date Application Submitted: October 23, 2007
Application Description: Kintama Research Corp Tenant Improvements - 455m2 suite - Work includes adding 161m2 second floor and 40m2 enclosed mezzanine. No FRR rating required for enclosed mezzanine; stairs, guard and handrail to comply with 2006 BCBC. Second floor 3/4 hr fire separation for floor and walls where facing open warehouse; 3/4 hr FRR for supports of 2nd floor system. Entrance lobby considered part of second floor to be separated from lower floor by 3/4 hr FS.

Building Classification 2006: 983m2, Group F-2, 3.2.2.72. 2 storey, sprinklered with fire alarm, < 1800m2, combustible construction, 45min. FS/FRR for floors if combustible. 4 hr firewall between strata units 5 & 6; west end 517m2, east end 983m2.

Physical File Scanned + attached Sep 23, 2008 db
Application Status: COMPLETED
Permit Value: $150,000.00
Building Area: 201.00 M2
2,163.54 ft2
Builder: ISLAND WEST COAST DEVELOPMENTS
Issued Date: December 03, 2007
File Close Date: February 12, 2008

Associated Properties

Address Zone More
10   1850 NORTHFIELD ROAD I3 Property Report

Process Steps

Task Status
UNDERSLAB PLUMBING

Complete underslab plumbing must be visible.

FAILED
UNDERSLAB PLUMBING

Complete underslab plumbing must be visible.

PASSED
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PARTIAL
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PARTIAL
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PARTIAL
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PASSED
ROUGH IN SPRINKLER

Rough in sprinkler must be complete and visible for inspection.

PASSED
FRAMING

Rough in plumbing and electrical must be complete. Survey Certificate and Truss Layouts required for approval.

PASSED
PLUMBING FINAL-OLD

All fixtures must be in place.

PARTIAL
PLUMBING FINAL-OLD

All fixtures must be in place.

PARTIAL
PLUMBING FINAL-OLD

All fixtures must be in place.

PASSED
SPRINKLER FINAL-OLD

Sprinkler system must be complete and operating as intended.

PARTIAL
SPRINKLER FINAL-OLD

Sprinkler system must be complete and operating as intended.

PASSED
FINAL-OLD

Final Approval as per requirements on plans.

PARTIAL
FINAL-OLD

Final Approval as per requirements on plans.

FAILED
FINAL-OLD

Final Approval as per requirements on plans.

PARTIAL
FINAL-OLD

Final Approval as per requirements on plans.

PASSED

2008-02-12

Map
View in Google Earth (KML)


Disclaimer:

The City of Nanaimo does not endorse any information contained herein by parties not affiliated with the City of Nanaimo. Furthermore, the City of Nanaimo is providing the information contained within this website without warranty, guarantee, or further obligation. The City is not liable for any consequences or damages any individual may incur as a result of misrepresented, misquoted, or mistaken information.