BP110228 - 6205 Oliver (formerly 6201) -- Drawings scanned/attached

Interested in this application? Login to manage subscriptions to subscribe to updates!

Search Again
BP110228 - 6205 Oliver (formerly 6201) -- Drawings scanned/attached
Neighbourhood: Rutherford    
Street Address: 6205 Oliver (formerly 6201) -- Drawings scanned/attached
Type of Application: Commercial / Multi / Industrial
File Number: BP110228
Date Application Submitted: March 03, 2006
Application Description: Residential Seniors Facility-Phase 1 - 110 units
4 storey non-combustible Senior Residential Building 3.2.2.43 with underground parking in basement & amenities.
Group C Residential & basement parkade (future phase group F3 ), sprinklered to NFPA 13,Fire alarm system,Floor assemblies 1 Hour FRR/FS , Non combustible construction required,parking storage garage 1.5hr. FRR/FS.Vestibule required to parkade.Duct shafts 1 hour FRR/FS, dumbwaiter 1hr. FRR/FS,Linen chute and refuse chute 1 hr FRR/FS c/w closure with fusible links.Exits 1 hour FRR/FS, Residential Suites doors 20 min labelled FPR.
Sprinkler drawings issued 2006-Sept-20
changed on May 24, 2007.Professional Assurance of building envelope professional design review and commitment for enhanced field review by S.K.C. Li, P.Eng. (Schedule D).
ADDRESS CHANGED TO 6205 OLIVER ROAD FOR THIS PROJECT. (some time ago.)
Physical File Scanned + attached Dec 5, 2008 db
Application Status: COMPLETED
Permit Value: $12,000,000.00
Builder: KNAPPET INDUSTRIES LTD
Issued Date: July 24, 2006
File Close Date: January 21, 2008

Associated Properties

Address Zone More
6205 OLIVER ROAD R8 Property Report

Process Steps

Task Status
FOOTING/FORMS

Inspection of forms prior to any cement being poured. For footing inspection, forms must be complete and approved plans (complete with City stamp) must be onsite.

PARTIAL
PERIMETER DRAIN

For perimeter drain, foundation walls should be damp proofed and drain tile in place with drain rock covering.

PARTIAL
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PARTIAL
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PARTIAL
ROUGH IN PLUMBING

Rough in plumbing must be complete including potable water piping.

PARTIAL
ROUGH IN SPRINKLER

Rough in sprinkler must be complete and visable for inspection.

PARTIAL
ROUGH IN SPRINKLER

Rough in sprinkler must be complete and visable for inspection.

PARTIAL
ROUGH IN SPRINKLER

Rough in sprinkler must be complete and visable for inspection.

PARTIAL
ROUGH IN SPRINKLER

Rough in sprinkler must be complete and visable for inspection.

PARTIAL
ROUGH IN SPRINKLER

Rough in sprinkler must be complete and visable for inspection.

SCHEDULED
FRAMING

Rough in plumbing & electrical must be complete. Survey Certificate & Truss layouts required for approval.

CANCELLED
INSULATION

Insulation and vapour barrier to be complete prior to inspection.

CANCELLED
MONITORING FIELD REVIEW

A building official may attend the site from time to time during the course of construction to ascertain that the field reviews are taking place and to monitor the field reviews undertaken by the registered professional.

CANCELLED
MONITORING FIELD REVIEW

A building official may attend the site from time to time during the course of construction to ascertain that the field reviews are taking place and to monitor the field reviews undertaken by the registered professional.

PARTIAL
SPRINKLER FINAL-OLD

Sprinkler system must be complete and operating as intended.

CANCELLED
SPRINKLER FINAL-OLD

Sprinkler system must be complete and operating as intended.

PARTIAL
PLUMBING FINAL-OLD

All fixtures must be in place.

CANCELLED
PLUMBING FINAL-OLD

All fixtures must be in place.

PARTIAL
OCCUPANCY-OLD PARTIAL
OCCUPANCY-OLD FAILED
OCCUPANCY-OLD CANCELLED
OCCUPANCY-OLD PASSED

2008-01-22

FINAL-OLD

Final approval as per requirements on plans.

PARTIAL
FINAL-OLD

Final approval as per requirements on plans.

PASSED

2008-06-27

Map
View in Google Earth (KML)


Disclaimer:

The City of Nanaimo does not endorse any information contained herein by parties not affiliated with the City of Nanaimo. Furthermore, the City of Nanaimo is providing the information contained within this website without warranty, guarantee, or further obligation. The City is not liable for any consequences or damages any individual may incur as a result of misrepresented, misquoted, or mistaken information.